Case Studies

Genuine completed jobs from Synergy Gas & Plumbing — real faults, real diagnoses, real outcomes. No stock photography, no invented reviews. Where a job has a full write-up with the engineer's photos, the ticket links to it on synergygas.org.

Boiler repairGreat Barr

Vaillant ecoTEC 937 needing regular resets: F.62 and F.75, new PCB and pressure sensor

The last ten faults in the history were F.62 and F.75. Repaired and given a full strip-down service on one visit.

FaultFaulty PCB (F.62); blocked pressure sensor, with the pump working perfectly (F.75)
FixNew PCB from van stock, new pressure sensor, expansion vessel recharged, new burner seal
ResultA very happy customer, who booked services and landlord checks for their other properties. Photos and full write-up
Boiler repairGreat Barr

Baxi Solo HE 15 with no flow: the failed pump and pump valves replaced

A rental with no heating or hot water. Fixed on one visit, and the landlord and tenant were extremely happy.

FaultNo flow: the pump had 240 V but would not spin, and the pump valves had failed
FixDrained down; new pump and pump valves; refilled, bled, leak-checked and purged of air
ResultHeating and hot water back on one visit. Photos and full write-up
Boiler repairSolihull

A restaurant's Potterton Gold on E161: new fan, then a new PCB, the same day

No heating or hot water at a restaurant. Both parts fitted the same day, before opening time.

FaultE161, a fan fault; testing then found the PCB intermittently dropping the voltage to the pump
FixNew fan fitted; new PCB picked up and fitted the same day
ResultHeating and hot water working before opening time. Photos and full write-up
Boiler repairErdington

Main Combi 30 Eco Elite losing pressure: expansion vessel recharged, pressure relief valve replaced

The boiler kept going off, and the customer had to keep topping up the pressure. Booked as a breakdown and a service.

FaultExpansion vessel flat, and the pressure relief valve had failed
FixVessel recharged and the system repressurised; new pressure relief valve from van stock on the same visit
ResultRepaired and given a basic service on one visit, with the condensate trap cleared. Photos and full write-up
Boiler repairMoseley

Vaillant ecoTEC showing F.75: the original 18-year-old pump replaced

Booked in for a service, the boiler was found not working. Fixed the day before the customer went on a cruise.

FaultF.75: the original pump had failed after 18 years, and its automatic air vent was leaking
FixNew Vaillant high-efficiency pump with a new air vent, ordered and fitted on a second visit
ResultBoiler running again before the cruise. Photos and full write-up
Boiler repairGreat Barr

Potterton Gold: pressure rising even with the boiler off, pinholed plate heat exchanger replaced

The customer had been bleeding radiators to bring the pressure down, and expected to be told they needed a new boiler.

FaultA pinholed plate heat exchanger letting mains water into the heating circuit
FixNew plate heat exchanger and pressure relief valve, from the van, on one visit
ResultBoiler repaired, no new boiler needed. Photos and full write-up
Emergency boiler repairSutton Coldfield

Worcester Greenstar 30i ErP: fault C7 at 8.30pm, new fan and new PCB fitted within two hours

An evening call. The boiler was locked out on C7, a fan fault, and an H09 code had been coming back for months.

FaultFailed fan (C7); the PCB diagnosed as the cause of the H09 fault
FixNew fan and new PCB fitted on the same visit, genuine Worcester Bosch parts from the van
ResultBoiler running within two hours of the call. Photos and full write-up
Repair and power flushWolverhampton

Biasi Advance 25C: a new plate heat exchanger blocked within nine days, so the system was power flushed

A rental where we had already replaced a sludged diverter valve and plate heat exchanger. The landlord replaced the part without flushing the system, and the hot water failed again nine days later.

FaultThe new plate heat exchanger blocked with sludge from the heating system
FixWhole system power flushed; plate heat exchanger cleaned and refitted
ResultHot water working; magnetic filter fitted and inhibitor added to stop it happening again. Photos and full write-up
Emergency boiler repairSutton Coldfield

Potterton Assure: fault E133 on a Sunday, no heating or hot water, blocked condensate trap cleared

An out-of-hours call on a Sunday. The boiler was showing E133 and there was no heating or hot water.

FaultCondensate trap blocked with sludge and debris, so the boiler could not light
FixBlockage cleared and the boiler running again on the same visit
ResultHeating and hot water back; a service booked for the following week. Photos and full write-up
Service and repairSolihull

Vaillant ecoTEC pro 28: leaking, heating staying on with no demand, diverter valve replaced

We were there for the annual service, and the customer mentioned the boiler was leaking and the heating was staying on with nothing asking for it.

FaultDiverter valve with rust and corrosion around its ports, accounting for both the leak and the heating staying on
FixNew diverter valve fitted, expansion vessel checked at 1.00 bar
ResultFlue gas analysis CO/CO2 ratio 0.0005, comfortably inside the limit. Photos and full write-up
Emergency electric boiler repairJewellery Quarter, Birmingham

Potterton Gold electric boiler: overheat light flashing on a Saturday, sorted on one visit

An out-of-hours call on a Saturday. The overheat light was flashing when we arrived.

FaultLow system pressure, and a loose automatic air vent that leaked once the pressure came back up
FixPressure topped up, air vent tightened and checked dry
ResultHeating tested and all working. Photos and full write-up
Job ticketHandsworth, Birmingham

Worcester Greenstar 30i ErP: H09 fault, circuit board replaced in one visit

The customer's boiler was showing an H09 fault on its display.

FaultFaulty main circuit board
FixBoard carried on the van, new one fitted on the same visit
ResultCustomer back up and running in one visit. Photos and full write-up
Emergency boiler repairKingstanding, Birmingham

Worcester Greenstar 25i ErP: leaking after 10pm, fixed the same night

A customer called after 10pm with water leaking. We were on site within 30 minutes. They expected the water to be turned off at the stop tap and a return visit.

FaultLeak at the flow adapter on the boiler's right-hand manifold
FixPart carried on the van, replaced there and then, boiler back in service
ResultFixed on the first visit, the same night, and an extremely happy customer. Photos and full write-up
Heat interface unit repairNewtown, Birmingham

Meibes HIU: no hot water and leaks, five engineers before us, PM valve replaced

A customer in a Newtown apartment block on a heat network had no hot water and leaks from their Meibes heat interface unit. Five different engineers had already been out to try to diagnose it.

FaultPM valve on the hot water side with a joint patched in sealant and a hose clip
FixFailed valve taken out and a new PM valve fitted
ResultCustomer back up and running. Photos and full write-up
Hot water cylinder repairBirmingham city centre

Megaflo unvented cylinder: no hot water, both immersion elements replaced

Not every no-hot-water call is the boiler. A tenant in a city centre flat had no hot water from an electrically heated Heatrae Sadia Megaflo and asked us to replace both immersion elements.

FaultBoth immersion elements coated in scale and corrosion
FixCylinder isolated and drained down, both elements replaced by a G3-qualified engineer, refilled and both elements tested
ResultHot water back on the same visit and a very happy tenant. Photos and full write-up
Job ticketEdgbaston, Birmingham

Emergency gas leak: supply capped by Cadent, no heating or hot water

Existing customers smelt gas in their upstairs bathroom and called the gas emergency line. Cadent found a 20 mbar pressure drop on the internal pipework and capped the supply at the meter, which left the boiler off. They rang us and we attended the same day.

FaultGas escape on the old steel gas pipe inside the property
FixOld steel pipe capped off and the supply to the boiler kept; tightness tested with no pressure drop, then recommissioned
ResultHeating and hot water back the same day. The hob now needs a new gas supply, or an electric hob instead. Photos and full write-up
Job ticketWednesbury

Main Eco Compact 25: E118 low pressure, and no heating

The boiler had locked out on E118, Main and Baxi's low-pressure code. The customer could not top it up because the filling loop had been boxed in with the pipework. Once the pressure was back, the heating still would not come on: the wireless room thermostat had a blank screen.

FaultLow system pressure, filling loop hidden behind boxing; flat batteries in the wireless thermostat
FixFilling loop found, system topped up and checked for leaks; thermostat batteries replaced from van stock
ResultBoiler running and the heating back on in one visit, and a very happy customer. Photos and full write-up
Job ticketWolverhampton, WV10

Biasi Advance 25C: no hot water and Er 14 in a rental property

The tenant had heating but no hot water, and the boiler showed Er 14, the Advance range's circulation code. With the case off, the diverter valve was jammed with black magnetite sludge and the plate heat exchanger behind it was choked with the same.

FaultSludged diverter valve, then a blocked plate heat exchanger
FixDiverter valve replaced from van stock on the first visit; plate heat exchanger ordered and fitted on the second
ResultHot water back on day one and reliable after the second visit; system clean and magnetic filter recommended to the landlord. Photos and full write-up
Job ticketWalsall

Worcester Greenstar Ri: repeated ignition lockout, told it needed a new boiler

The customer had been told by previous engineers that the boiler was finished. It kept locking out on ignition. With the burner out, the burner gasket had perished and the electrode was damaged.

FaultPerished burner gasket and damaged ignition electrode
FixBoth replaced from van stock on the first visit, then tested through several ignition cycles
ResultRunning reliably, no new boiler needed. Photos and full write-up
Job ticketQuinton, Birmingham

Worcester Greenstar 30Si Compact: control panel held up with duct tape

Booked online as a repair. The control panel was hanging down, held with tape and a piece of copper pipe. A snapped hinge clip, a common failure on the Compact, and not a reason to replace the boiler.

FaultSnapped control panel hinge clip
FixBoth hinge clips replaced from van stock; condensate pipe insulation advised
ResultPanel secure, boiler inspected, customer reassured. Photos and full write-up
Job ticketStourbridge, DY8

Worcester CDi: no hot water and an EA fault on the display

A returning customer with no hot water and EA showing. After the safety checks the fault traced to the gas valve, which is not a van-stock part on this model.

FaultFaulty gas valve
FixCorrect valve ordered and fitted on a return visit, followed by tightness, leak and operation checks
ResultHot water restored and the boiler signed off safe. Photos and full write-up
Job ticketWalsall (rental)

Overheat lockout on a landlord's boiler: the pump had burnt out

The tenant reported a boiler locking out on overheat. The system pump was found burnt out, choked with the sludge that had been circulating for years.

FaultFailed pump, packed with magnetite sludge
FixNew pump fitted from van stock on the same visit; system flush recommended to the landlord
ResultHeating back the same day; the landlord told plainly the repair was avoidable with maintenance. Photos and full write-up
Job ticketSolihull

Worcester Greenstar 28i Junior: leaking inside the case

Water inside the boiler case. The right-hand hydraulic manifold had corroded and was weeping at the joints, and the part is not one we carry.

FaultCorroded right-hand manifold
FixManifold sourced locally the same day, collected and fitted, boiler refilled and tested dry
ResultFixed in one day with no return visit. Photos and full write-up
Job ticketStourbridge (rental)

Worcester CDi: leak flagged on a gas safety check, traced to the condensate collector

Another engineer had noted a leak on the landlord's safety check. On the follow-up we traced it to the condensate collector inside the combustion box, whose seals had perished.

FaultDeteriorated condensate collector seals
FixCombustion box stripped, collector and seals replaced, box rebuilt and combustion proved on the analyser
ResultCO 79 ppm and a clean ratio on the analyser after the rebuild. Photos and full write-up
Job ticketChelmsley Wood (rental)

Glow-worm found producing carbon monoxide on a landlord inspection

Rust at the back of the heat exchanger and a CO reading on the analyser, in a house with a young family. Made safe on the spot, then repaired with the landlord's go-ahead.

FaultCracked flue collector letting combustion products escape
FixBoiler capped off and made safe; flue collector and gaskets replaced, then retested on the analyser
ResultBack in service safely rather than condemned, tenant and landlord both informed throughout. Photos and full write-up
Job ticketStourbridge, DY8

Ariston Evo combi: no hot water and overheating, fixed in one visit

The customer's Ariston Evo combi boiler had stopped producing hot water — every time a hot tap was opened, the boiler overheated instead. A fault like this can look like several different things before it's properly diagnosed.

FaultBlocked plate heat exchanger
FixPlate heat exchanger replaced — part collected mid-visit rather than booking a return trip
ResultHot water fully restored, completed in a single appointment
Job ticketErdington, Birmingham

Gledhill Pulsacoil electric boiler: total loss of hot water

The customer had no hot water at all from their Gledhill Pulsacoil electric boiler — a less common system that a lot of general boiler repair companies aren't set up to work on.

FaultCorroded immersion heater
FixImmersion heater replaced, full system tested before leaving
ResultFull hot water flow restored the same day
Job ticketSutton Coldfield

Emergency boiler breakdown replaced with a new Worcester LPG combi

The customer's existing boiler broke down and needed replacing as an emergency, rather than a planned installation.

FaultEnd-of-life boiler failure
FixNew energy-efficient Worcester LPG combi installed, backed by a 10-year manufacturer guarantee
ResultReliable heating and hot water restored, lower running costs, long-term warranty cover
Job ticketDudley

Gas leak traced to a damaged copper line beneath the floorboards

The customer reported a suspected gas leak, with the source not visible or accessible from above the floor.

FaultDamaged section of copper gas pipe under the floor
FixDamaged pipe section safely repaired, system checked to confirm the leak was fully resolved
ResultLeak fully resolved, gas supply safe again
24/7 Emergency Repair

Need an engineer?

Same opening hours as Synergy Gas & Plumbing — you're speaking to the same team regardless of which site you found us through.

Office hours
Mon–Fri, 8am–5pm
Emergencies
24 hours, 7 days a week
Out of hours
Call 07413 385767 — we'll quote before coming out, no surprises
📞 Call 07413 385767 💬 WhatsApp

Get a Callback

📞 07413 385767Call now 🔧 Request a repairNon-urgent jobs